Publicações por Orlando Frazão

2010

Acoustic Source Location of Partial Discharges in Transformers

Autores
Lima, SEU; Frazao, O; Farias, RG; Araujo, FM; Ferreira, LA; Miranda, V; Santos, JL;

Publicação
FOURTH EUROPEAN WORKSHOP ON OPTICAL FIBRE SENSORS

Abstract
Acoustic emission monitoring is often used in the diagnosis of electrical and mechanical incipient faults in high voltage apparatus. Partial discharges are a major source of insulation failure in power transformers and the differentiation from other sources of acoustic emissions is of the utmost importance. Also, it is important to give an indication of the PD source location in order to obtain a useful diagnosis. This paper reports the developments in partial discharges source location through the associated acoustic emissions using three different algorithms.

2010

Fibre laser sensor based on a phase-shifted chirped grating for acoustic sensing of partial discharges in power transformers

Autores
Lima, SEU; Frazao, O; Farias, RG; Araujo, FM; Ferreira, LA; Miranda, V; Santos, JL;

Publicação
FOURTH EUROPEAN WORKSHOP ON OPTICAL FIBRE SENSORS

Abstract
Partial discharges are a major source of insulation failure in electric power transformers. Their detection can be achieved through the associated acoustic emissions, and this work reports on the investigation of a fibre laser sensor based on a phase-shifted chirped fibre grating for acoustic emission detection in the power transformer environment. The performance of the sensing head is characterized and compared for different surrounding media: air, water and oil.

2008

Fibre Fabry-Perot sensor for acoustic detection

Autores
Lima, SEU; Frazao, O; Araujo, FM; Ferreira, LA; Miranda, V; Santos, JL;

Publicação
19TH INTERNATIONAL CONFERENCE ON OPTICAL FIBRE SENSORS, PTS 1 AND 2

Abstract
Incipient fault diagnosis is closely related to isolation condition assessment. There are a great number of methods available for condition monitoring and diagnosis of power transformer isolation systems, but only few of them can take direct measurements inside the transformer. Fibre optic sensors can be applied to incipient fault diagnosis. In special, acoustic sensors are being developed for the detection and location of partial discharges in oil-filled power transformers. Towards such objective, this work reports investigation on the applicability of fibre Fabry-Perot interferometers for acoustic detection both in air and in liquids.

2023

Vernier Effect in a Compact Strain Sensor Based on Fiber Loop Mirrors Using a 3 x 3 Coupler

Autores
Soares, B; Silva, S; Ribeiro, P; Frazao, O;

Publicação
IEEE PHOTONICS TECHNOLOGY LETTERS

Abstract
In this letter, a new configuration based on two fiber loop mirrors in series using a 3x3 coupler is demonstrated. This configuration is compact and can explore the Vernier effect. The results obtained were a sensitivity of 74.9 +/- 0.2 pm/ mu epsilon for the Vernier envelope and 6.41 +/- 0.01 pm/mu epsilon for the Vernier carrier. These results were compared to the sensitivity of the setup using only one fiber loop mirror interferometer, obtaining 14.41 +/- 0.01 pm/mu epsilon. This means a magnification factor of 5.2 for the Vernier envelope. Theoretical treatment of the system was carried out, using Jones matrix calculus, and the subsequent simulation results are also presented, having obtained good agreement with the experimental data.

2020

Challenging the Limits of Interferometric Fiber Sensor Sensitivity with the Optical Harmonic Vernier Effect

Autores
Gomes, AD; Ferreira, MS; Bierlich, J; Kobelke, J; Rothhardt, M; Bartelt, H; Frazão, O;

Publicação
Optics InfoBase Conference Papers

Abstract
We discuss the novel concept of harmonics of the Vernier effect for optical fiber sensors as a tool to break the limits of conventional optical Vernier effect currently used. The new effect provides enhancements scalable with the harmonic order. © 2021 The Author(s).

2023

Refractive Index Measurements of Ethanol-Water Binary Liquid Solutions Using a Graded-Index Fiber Tip Sensor

Autores
Soares, L; Cunha, C; Novais, S; Ferreira, A; Frazao, O; Silva, S;

Publicação
IEEE SENSORS LETTERS

Abstract
The refractometric analysis of ethanol-water mixtures is hampered because this type of binary solution does not present a linear behavior. In this letter, a multimode graded-index fiber (GIF) tip sensor for the measurement of ethanol in binary liquid solutions of ethanol-water is proposed. The proof is fabricated by the fusion-splicing of a 500 mu m GIF to a single-mode fiber (SMF), and it operates as a refractometric sensor in reflection. To evaluate the prove potential to detected ethanol variations, samples of ethanol-water mixtures were measured at different temperatures (20 degrees C-60 degrees C). The samples have different %(v/v) of ethanol, in a range between 0% and 100%.