Cookies
O website necessita de alguns cookies e outros recursos semelhantes para funcionar. Caso o permita, o INESC TEC irá utilizar cookies para recolher dados sobre as suas visitas, contribuindo, assim, para estatísticas agregadas que permitem melhorar o nosso serviço. Ver mais
Aceitar Rejeitar
  • Menu
Publicações

Publicações por José Luís Santos

2009

Extrinsic and intrinsic fiber optic interferometric sensors for acoustic detection in high-voltage environments

Autores
Lima, SEU; Frazao, O; Araujo, FM; Ferreira, LA; Miranda, V; Santos, JL;

Publicação
OPTICAL ENGINEERING

Abstract
Incipient fault diagnosis is closely related to insulation condition assessment. A great number of methods are available for condition monitoring and diagnosis of power transformer insulation systems, but only few of them can take direct measurements inside the transformer. Fiber optic sensors can be applied to incipient fault diagnosis. In particular, acoustic sensors have been developed for detection and location of partial discharges in oil-filled power transformers. We report the study of extrinsic and intrinsic fiber Fabry-Perot sensors that can be used to detect the acoustic waves that are generated by a partial discharge inside a power transformer. A comparative analysis is done to determine the best sensing head configuration and some methods to improve the parameter readout sensitivity are proposed. The sensing head behaviour when immersed in different fluids (air, water, and oil) is also investigated. (c) 2009 Society of Photo-Optical Instrumentation Engineers. [DOI: 10.1117/1.3080752]

2010

Mandrel-Based Fiber-Optic Sensors for Acoustic Detection of Partial Discharges - a Proof of Concept

Autores
Lima, SEU; Frazao, O; Farias, RG; Araujo, FM; Ferreira, LA; Santos, JL; Miranda, V;

Publicação
IEEE TRANSACTIONS ON POWER DELIVERY

Abstract
Acoustic emission monitoring is often used in the diagnosis of electrical and mechanical incipient faults in high-voltage apparatus. Partial discharges are a source of failure in power transformers, and the differentiation from other sources of acoustic emissions is of the utmost importance. This paper reports the development of a new sensor concept-mandrel-based fiber-optic sensor-for the detection of incipient faults in oil-filled power transformers, taking direct measurements inside a transformer. These sensors can be placed in the inner surface of the transformer tank wall, not affecting the insulation integrity of the structure, and improving fault detection and location. The applicability of these acoustic sensors in air, water, and oil is investigated and the paper presents the promising results obtained, which will enable the industrial development of practical solutions.

2009

Fiber Fabry-Perot Sensors for Acoustic Detection of Partial Discharges in Transformers

Autores
Lima, SEU; Frazao, O; Farias, RG; Araujo, FM; Ferreira, LA; Santos, JL; Miranda, V;

Publicação
2009 SBMO/IEEE MTT-S INTERNATIONAL MICROWAVE AND OPTOELECTRONICS CONFERENCE (IMOC 2009)

Abstract
Acoustic emission monitoring is often used in the diagnosis of electrical and mechanical incipient faults in high voltage apparatus. A great number of methods are available for condition monitoring and diagnosis of power transformer insulation, but only a few can take direct measurements inside a transformer. Partial discharges are a major source of insulation failure in power transformers and their detection can be achieved through the associated acoustic emissions. This paper reports the development of two sensing head configurations based on extrinsic and intrinsic fiber Fabry-Perot interferometers for the detection of incipient faults in oil-filled power transformers. These sensors can be placed inside the transformer tank without affecting the insulation integrity, improving fault detection and location. The performances of the sensing heads are characterized and compared with the situations where it operates in air, water and oil and promising results are obtained, which will allow the industrial development of practical solutions.

2010

INTRINSIC AND EXTRINSIC FIBER FABRY-PEROT SENSORS FOR ACOUSTIC DETECTION IN LIQUIDS

Autores
Lima, SEU; Frazao, O; Farias, RG; Araujo, FM; Ferreira, LA; Miranda, V; Santos, JL;

Publicação
MICROWAVE AND OPTICAL TECHNOLOGY LETTERS

Abstract
This article reports the development of two sensing head configurations based on extrinsic and intrinsic fiber Fabry-Perot interferometers for the detection of incipient faults in oil-filled power transformers. The performances of the sensing heads are characterized and compared with the situations where it operates in air, water, and oil and promising results are obtained, which will allow the industrial development of practical solutions. (C) 2010 Wiley Periodicals, Inc. Microwave Opt Technol Lett 52: 1129-1134, 2010; Published online in Wiley InterScience (www.interscience.wiley.com). DOI 10.1002/mop.25139

2010

Acoustic Source Location of Partial Discharges in Transformers

Autores
Lima, SEU; Frazao, O; Farias, RG; Araujo, FM; Ferreira, LA; Miranda, V; Santos, JL;

Publicação
FOURTH EUROPEAN WORKSHOP ON OPTICAL FIBRE SENSORS

Abstract
Acoustic emission monitoring is often used in the diagnosis of electrical and mechanical incipient faults in high voltage apparatus. Partial discharges are a major source of insulation failure in power transformers and the differentiation from other sources of acoustic emissions is of the utmost importance. Also, it is important to give an indication of the PD source location in order to obtain a useful diagnosis. This paper reports the developments in partial discharges source location through the associated acoustic emissions using three different algorithms.

2010

Fibre laser sensor based on a phase-shifted chirped grating for acoustic sensing of partial discharges in power transformers

Autores
Lima, SEU; Frazao, O; Farias, RG; Araujo, FM; Ferreira, LA; Miranda, V; Santos, JL;

Publicação
FOURTH EUROPEAN WORKSHOP ON OPTICAL FIBRE SENSORS

Abstract
Partial discharges are a major source of insulation failure in electric power transformers. Their detection can be achieved through the associated acoustic emissions, and this work reports on the investigation of a fibre laser sensor based on a phase-shifted chirped fibre grating for acoustic emission detection in the power transformer environment. The performance of the sensing head is characterized and compared for different surrounding media: air, water and oil.

  • 81